Star-34 venting supplement, Select vent method – Weil-McLain STAR-34 User Manual

Page 5

background image

Part Number 550-110-268/0699

5

StaR-34 Venting Supplement

26801

Air pipe

Vent pipe

StaR-34
vent starter tee

Slope

Slope vent pipe downward, toward
boiler, minimum ¼” per foot.

Figure 3

GV direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)

Figure 5

GV direct vent

(using Weil-McLain

Through-Roof or Through-Unused-
Chimney Termination Kit)

26803

Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.

StaR-34
vent starter tee

Select

vent

method

Figure 7

GV non-direct vent through roof

26805

Slope vent pipe
downward,
toward boiler,
minimum ¼”
per foot.

StaR-34
vent starter tee

26804

Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.

StaR-34
vent starter tee

Figure 6

GV non-direct vent through sidewall
(using termination coupling)

(See WARNING above.)

26802

Vent pipe

StaR-34
vent starter tee

Slope

Slope vent
pipe
downward,
toward boiler,
minimum ¼”
per foot.

Figure 4

GV non-direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)

(See WARNING above.)

For altitudes more than 5,500 feet above sea level —

Do not

use non-direct vent through

sidewall methods as shown in

Figures 4

and

6

below. Can cause severe personal injury, death

or substantial property damage if ignored.