Star-34 venting supplement, Select vent method – Weil-McLain STAR-34 User Manual
Page 5
Part Number 550-110-268/0699
5
StaR-34 Venting Supplement
26801
Air pipe
Vent pipe
StaR-34
vent starter tee
Slope
Slope vent pipe downward, toward
boiler, minimum ¼” per foot.
Figure 3
GV direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)
Figure 5
GV direct vent
(using Weil-McLain
Through-Roof or Through-Unused-
Chimney Termination Kit)
26803
Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.
StaR-34
vent starter tee
Select
vent
method
Figure 7
GV non-direct vent through roof
26805
Slope vent pipe
downward,
toward boiler,
minimum ¼”
per foot.
StaR-34
vent starter tee
26804
Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.
StaR-34
vent starter tee
Figure 6
GV non-direct vent through sidewall
(using termination coupling)
(See WARNING above.)
26802
Vent pipe
StaR-34
vent starter tee
Slope
Slope vent
pipe
downward,
toward boiler,
minimum ¼”
per foot.
Figure 4
GV non-direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)
(See WARNING above.)
For altitudes more than 5,500 feet above sea level —
Do not
use non-direct vent through
sidewall methods as shown in
Figures 4
and
6
below. Can cause severe personal injury, death
or substantial property damage if ignored.