beautypg.com

Vent termination, Star-34 venting supplement, Venting method definitions – Weil-McLain STAR-34 User Manual

Page 3: Properly locate vent termination

background image

Part Number 550-110-268/0699

3

StaR-34 Venting Supplement

Vent termination

Venting method definitions

Direct vent

— Uses outside combustion air with combustion

air connector piping sealed at all joints and seams. Also known as
“sealed combustion”.

Non-Direct vent

— Uses inside combustion air with no

combustion air connector piping.

Figure 1

Vent termination locations

26807

Snow

1 foot

1 f

t

1 f

t

1 ft

Properly locate vent termination

Follow instructions on this page when
determining vent location to avoid possibility
of severe personal injury, death or substantial
property damage.

1. When using direct vent method — Refer to separate

instructions packed with Weil-McLain direct vent termination
kit and vent pipe manufacturer's instructions for additional
locations.

2. For location of non-direct vent vertical termination, see vent

pipe manufacturer's instructions.

3. Gases will form white plume in winter. Plume could obstruct

window view.

4. Prevailing winds could cause freezing of condensate and

water/ice buildup on building, plants or roof.

5. Locate or guard vent to prevent accidental contact by people

or pets.

6. Do not terminate vent in window well, stairwell, alcove,

courtyard, or other recessed areas.

7. Non-Direct vent installations only — Vent must terminate

more than 1 foot below or to side of all doors or windows.
See

Figure 1

.

8. Vent must terminate more than 1 foot above grade or

anticipated snow line. In addition, vent termination must be
at least 7 feet above public walkway and 3 feet above any forced
air intake within 10 feet. Stay well away from trees, shrubs,
and decorative items. Site conditions may dictate greater
clearances. See

Figure 1

.

9. Vent must terminate at least 4 feet horizontally, and in no

case above or below, unless a 4 foot horizontal distance is
maintained, from electric meters, gas meters, regulators, relief
valves, and other equipment.

10. Locate or guard vent to prevent condensate from damaging

exterior finishes.

11. Do not extend exposed vent pipe outside of building.

Condensate could freeze and block vent pipe.

12. Vent must terminate at least 6 feet away from adjacent walls.
13. Do not terminate vent closer than 5 feet below roof overhang.
14. Do not terminate vent above any door or window. Condensate

can freeze, causing ice formations.

15. Do not use existing chimney as raceway if another appliance

or fireplace is vented into or through chimney.

16. Do not connect:

Any other appliance to vent pipe.

Multiple boilers to a common vent pipe.

17. Do not wrap or insulate vent pipe and fittings.
18. Canadian installations — See CAN/CGA B149.1 or B149.2

Installation Code.

19.

A gas vent extending through an exterior
wall shall not terminate adjacent to the wall
or below building extensions such as eaves,
parapets, balconies or decks. Failure to
comply could result in severe personal
injury, death or substantial property
damage.

26808

Forced

air intake

Pu

blic

W

alk

wa

y

3 feet

If within 10 feet

7 feet