Prepare boiler location — codes & checklist

1a

Installations must follow these codes:

• Local, state, provincial, and national codes, laws, regulations and ordinances.

• National Fuel Gas Code, ANSI Z223.1–latest edition.

• Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/

ASME CSD-1, when required.

• National Electrical Code.

• For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian

Electrical Code Part 1 and any local codes.

The CGi-4E boiler gas manifold and controls met safe lighting

and other performance criteria when boiler underwent tests

specified in ANSI Z21.13–latest edition.

Read and follow the special instructions for the Commonwealth
of Massachusetts, located on page 42 of this manual.

Before locating the boiler, check the

following:

• Check for nearby connection to:

• System water piping

• Venting connections

• Gas supply piping

• Electrical power

• Check area around boiler.

Remove any combustible materials, gasoline and

other flammable liquids, or other contaminants

.

Failure to keep boiler area clear and free of

combustible mate

-

rials, gasoline and other flammable liquids and vapors

can

result in severe personal injury, death or substantial property

damage.

• Boiler must be installed so that gas control system components are protected

from dripping or spraying water or rain during operation or service.

• If new boiler will replace existing boiler, check for and correct system problems,

such as:

1. System leaks causing oxygen corrosion or section cracks from hard water

deposits.

2. Incorrectly-sized expansion tank.

3. Lack of antifreeze in boiler water causing system and boiler to freeze and

leak.