Watlow Electric Gateway & DeviceNet User Manual
Page 8

RUI/Gateway & DeviceNet
TM
Configuration & Ladder Logic Example
Using an Allen-Bradley CompactLogix PLC
Watlow 
1241 Bundy Blvd 
Winona, MN 55987 
Telephone: 507-494-5656 
© 2007 Watlow Electric Mfg Co 8 
4/08
 
15. Once the available device (RUI/Gateway in this case) is moved over to the Scanlist the next 
step will be to map the RUI/Gateway input and output bytes to PLC addresses; first the 
inputs. In this particular case the Automap on Add box was checked and the result of that now 
becomes apparent. Since there were no other devices on the network the software simply 
took all of the available RUI/Gateway input bytes (84) and allocated them to the first available 
PLC input bytes. Although we can’t see in the graphic below all of the addresses assigned 
you can trust that what was assigned are addresses 1:I.Data[0] through 1:I.Data[20]. If there 
were other devices on the network and the Automap on Add box was not checked the 
address field below would not be populated. Clicking on the Advanced button would then 
allow for manual configuration. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
16. Likewise, all of what was said above regarding the inputs also applies to the outputs as well. 
Notice in the graphic below that for the outputs the size changes to 80 bytes or 20-32 bit 
words and addresses given would be 1:O.Data[0] through 1:O.Data[19]. Click on the OK 
button where you will then be prompted to write this configuration to the scanner memory.
