RUI/Gateway & DeviceNet

TM

Configuration & Ladder Logic Example

Using an Allen-Bradley CompactLogix PLC

Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2007 Watlow Electric Mfg Co 12

4/08


22. Notice too, the slot number, in this case “1”. This is the physical slot in which the scanner

resides. After the scanner is configured two tags will be automatically generated reflecting the
existence of the scanner in slot 1 of the I/O structure. These tags will be used to move the
implicit input and output assemblies (more on this to follow) to and from the RUI/Gateway and
then ultimately to the destination EZ-ZONE

®

PM controls that exist on Standard Bus.














23. Before we get started with the programming examples it is important to note that the EZ-
ZONE

®

family of controls has an on-board EEPROM to back up user settings in the event of

a power loss. By default, the non-volatile save parameter is enabled, therefore changes made

over the network as well as any changes made from the RUI are saved to the EEPROM. If

the implicit output (PLC to EZ-ZONE

®

Control) assembly is in use, where information is

exchanged implicitly (continuously after the connection is established) the rate at which writes

to EEPROM occur could be very fast. With this being said, it should be considered carefully
as to whether or not this parameter should remain enabled. To avoid premature EEPROM
failure (~1,000,000 writes) it is recommended that the user disable the non-volatile write

parameter in the destination nodes residing on the Standard Bus side of the RUI/Gateway. An
example will follow showing how to read and write to this parameter.


EZ-ZONE

®

EEPROM