Pressure Testing gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG

1. Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in

excess of 1/2 psig will damage heater regulator.

2. Cap off open end of gas pipe where manual shutoff valve was connected.

3. Pressurize supply piping system by either using compressed air or

opening propane supply tank valve.

4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints.

Bubbles forming show a leak.

5. Correct all leaks at once.

6. Re-connect heater and manual shutoff valve to gas supply. Check re-connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1. Close manual shutoff valve (see Figure 14).

2. Pressurize supply piping system by either using compressed air or opening propane supply tank valve.

3. Check all joints from propane supply tank to manual shutoff valve (see Figure 15). Apply mixture of

liquid soap and water to gas joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Pressure Testing Heater Gas Connections

1. Open manual shutoff valve (see Figure 14).

2. Open propane supply tank valve.

3. Make sure control knob of heater is in the OFF position.

4. Check all joints from manual shutoff valve to gas control (see Figure 14). Apply mixture of liquid soap

and water to gas joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light heater (see Operating Heater, pages 18 through 21). Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appliance, page 20).

INSTALLING

Continued

Figure 14 - Manual Shutoff Valve

Figure 15 - Checking Gas Joints