Installation space

Ensure there is sufficient space to install the unit and to perform maintenance work as and when required.

Keep 15mm or more for clearance between top plate of the indoor unit and the ceiling surface.

Installation space

1000

or more

15 or more

15 or more

1000 or more

Obstacle

283

or more

283

or more

1000 or more

Ceiling height

When the ceiling height exceeds the standard distance of a 4-way discharge cassette as detailed in the following
table. The air-flow may not be sufficient to heat the room. It is therefore necessary to set the unit to high ceiling
mode or adjust the direction of the ceiling discharge.

If fitting a separately supplied filter, it will also be necessary to set to high ceiling mode.

For setup of the high ceiling mode, refer to the details of Applicable controls “To incorporate a filter sold separately”
and “In case of installation to high ceiling” within this Manual.

Installable ceiling height list

(Unit: m)

REQUIREMENT

• When high ceiling (1) or (3) is used with 4-way blowing, a draft is easily recognized due to drop of discharge

temperature.

The air filter cleaning signal duration (Notification of filter cleaning) on the remote controller can be changed
according to the condition of installation.

If the room is not heated due to the installation place or construction of the room, the detection temperature of
heating can be raised.

For setup method, refer to “Change of lighting term of filter sign” and “To secure better effect of heating” in the
Applicable controls of this Manual.

Model MMU-

0071 to 0121 type

0151 to 0181 type

Installable ceiling height

Up to 2.7 m

Up to 3.5 m

Indoor unit Capacity type

Discharge direction

Standard (At shipment)

High ceiling (2)

High ceiling (3)

0071 to 0121 type

0151 type

0181 type

4-way

3-way

2-way

4-way

3-way

2-way

4-way

3-way

2-way

2.7

2.9

3.2

3.2

3.4

3.5

3.5

Setup of high ceiling

Setup data

0000

0002

0003