Caution, Drain piping work – Toshiba MMU-AP0071MH User Manual

Page 14

background image

11

Thermal insulating process

• After checking of the draining, using the supplied thermal insulation fit to the flexible hose leaving no clearance at

the connecting port of the indoor unit.

• Fit locally procured thermal insulation to the drain pipe leaving no clearance between the supplied insulation.

Flexible hose

Hose band

Attached heat insulator Heat insulator to be

procured locally

Hard vinyl chloride pipe

CAUTION

Ensure water is poured slowly.

To reduce risk of water spreading throughout the
unit, resulting in a possible fault.

4

DRAIN PIPING WORK

Water (1500cc to 2000cc)

Insert the leading part of the
hose between the heat
exchanger and the drain pan,
and then bend it downward.

Check panel

Polyethylene hand pump for
pouring water in drain pan

Vessel

Drain pan

Air

discharge area