background image

15

Power supply specifications

Power supply wiring and communication wiring are to be procured locally.

For the power supply specification, follow the table below. Ensure power supply is adequate. An insufficient power
supply could result in unit failure.

For specification of the power capacity of the outdoor unit and the power supply wires, refer to the Installation
Manual supplied with the outdoor unit.

Indoor unit power supply

(*1)

• Indoor unit power supply, must have a dedicated supply and be separate to that of the outdoor unit.

• Arrange the power supplies to the indoor and outdoor units, so that a common earth leakage breaker and main

switch can be used.

• Power supply cable specification : Cable 3-core 2.5 mm², in conformity with Design 60245 IEC 57.

Indoor/Outdoor inter-unit wiring, Central controller wiring

(*2) (*3)

• Use a 2 core non polarity cable.

• To prevent any possible noise issues, use a shielded 2 core wire.

• The total stated length of communication wiring is determined by the interconnecting length of indoor to outdoor

cable plus the length of the central control communication cable.

Remote controller wiring

(*4)

• For wiring remote controllers a 2 core polarity cable must be used.

Remote controller inter-unit wiring

Indoor unit

Remote

controller

Indoor unit

L1

L2

Ln

(Max. 8 units)

Indoor unit

Indoor unit

Remote
controller
wiring

CAUTION

The remote controller wire
(Communication line) and AC220–
240V (Power supply) wires cannot
be parallel to contact each other
and cannot be stored in the same
conduits. If doing so, a trouble
may be caused on the control
system due to noise, etc.

6

ELECTRIC WORK

Indoor unit power supply (*1)

Communication line

Power supply

220–240V, 1N ~ 50Hz

220V, 1N ~ 60Hz

Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for indoor
units should be selected by the accommodated total current values of the indoor units.

Power supply wiring

20 m or less

Twist wire : 2.0 mm²

50 m or less

Twist wire : 3.5 mm²

Q’ty

2

Indoor/Outdoor inter-unit wiring (*2)

Wire size

(Up to 1000 m) Twist wire : 1.25 mm²
(Up to 2000 m) Twist wire : 2.0

0

mm²

Q’ty

2

Central control line wiring (*3)

Wire size

(Up to 1000 m) Twist wire : 1.25 mm²
(Up to 2000 m) Twist wire : 2.0

0

mm²

Remote controller wiring (*4)

Q’ty

2

Wire size

Twist wire : 0.5 to 2.0 mm²

Twist wire: 0.5mm

2

to 2.0 mm

2

× 2

Total wire length of remote controller
wiring and remote controller inter-unit
wiring = L + L1 + L2 + … Ln

In case of wired type only

In case of wireless type included

Remote controller wiring, remote
controller inter-unit wiring

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 500 m

Up to 400 m

Up to 200 m