Specifications – Tripp Lite 5kVA User Manual
Page 25
25
Specifications
The models listed below include a power module, one or two battery modules, and a transformer module. All models include all three
types of modules, with the exception of hardwired (HV) models, which do not include transformer modules. Depending on the model
ordered, the included battery module may be either expandable or nonexpandable. However, if extended runtime is required, all power mod-
ules are fully compatible with expandable Tripp Lite battery modules (Tripp Lite Model # BP240V10RT-3U, sold separately)
Model Information
Model #(s)
SU5000RT3UHV* & SU5000RT3U
SU6000RT3UHV* & SU6000RT3U
SU6000RT3UXR
SU10KRT3UHV* & SU10KRT3U
Package Includes:
Power Module
(model: SU5000RT3UPM;
(model: SU6000RT3UPM;
(model: SU6000RT3UPM;
(model: SU10KRT3UPM;
series: AGPS5124)
series: AGSU60003U)
series: AGSU60003U)
series: AGSU100003U)
Battery Module #1
(model: BP240V5RT2U;
(model: BP240V7RT3U;
(model: BP240V10RT-3U;
(model: BP240V10RT-3U;
series: AGBP5161)
series: AGBP240V7RT3U) series: AGBP240V7RT3U)
series: AGBP240V7RT3U)
Non-expandable
Non-expandable
Non-expandable
EXPANDABLE
Battery Module #2
N/A
N/A
(model: BP240V7RT3U;
N/A
series: AGBP240V7RT3U)
EXPANDABLE
Transformer Module
(model: SU5000XFMRT2U;
(model: SU6000XFMRRT3U;
(model: SU6000XFMRRT3U;
(model: SU10KXFMRRT3U;
series: AGAC5125) series: AGSM6000SDRT3U)
series: AGSM6000SDRT3U)
series: AGSM10KSDRT3U)
Approvals: All power modules (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC Class A). All battery modules except BP240V5RT2U (UL, cUL, NOM). All transformer modules (UL,
cUL, NOM, FCC Class A) * Transformer module not included with hardwired (HV) models.
Input
Input Connection Type
10 ft. cord with L6-30P plug
Hardwire
Hardwire
Hardwire
Input Voltage Range
156V~276V Single Phase
156V~276V Single Phase
156V~276V Single Phase
156V~276V Single Phase
Module Input Voltage
200/208/240V AC
200/208/240V AC
200/208/240V AC
200/208/240V AC
Input Frequency
50/60 Hz ± 3 Hz
50/60 Hz ± 3 Hz
50/60 Hz ± 3 Hz
50/60 Hz ± 3 Hz
Input Current
20A
22.6A
22.6A
40A
Inrush Current
<150A
<150A
<150A
<200A
Power Factor (Full Load)
>0.97
>0.97
>0.97
>0.97
Efficiency (Full Load/On-Line)
>87%
>87%
>87%
>88%
Power Module Circuit Breaker
N/A
40A (2 pole)
40A (2 pole)
63A (2 pole)
Transformer Module Circuit Breaker
N/A
40A (2 pole)
40A (2 pole)
63A (2 pole)
Output
VA
5000
6000
6000
10000
Watts (Power Factor: 0.7)
3500
4200
4200
7000
Output Connection Type
4 receptacles on power module
Hardwire
Hardwire
Hardwire
(2 L6-20R and 2 L6-30R) &
12 receptacles on transformer
module (5-15/20R)
Waveform (On-Line)
Sinewave
Sinewave
Sinewave
Sinewave
Waveform (On-Battery)
Sinewave
Sinewave
Sinewave
Sinewave
Output Voltage (RMS)
120*/200/208/240V AC
100/120/200/208/240V AC
100/120/200/208/240V AC
100/120/200/208/240V AC
Output Frequency
50/60 Hz (± 0.2 Hz on battery)
50/60 Hz (± 0.2 Hz on battery)
50/60 Hz (± 0.2 Hz on battery)
50/60 Hz (± 0.2 Hz on battery)
Voltage Regulation
±3%
±3%
±3%
±3%
Max. Harmonic Distortion
(Linear Full Load)
<3%
<3%
<3%
<3%
(Non-Linear Full Load)
<6%
<6%
<6%
<6%
Overload Capabilities
102% (continuous)
102% (continuous)
102% (continuous)
102% (continuous)
102%~125% (1 min.)
102%~125% (1 min.)
102%~125% (1 min.)
102%~125% (1 min.)
125%~150% (30 sec.)
125%~150% (30 sec.)
125%~150% (30 sec.)
125%~150% (30 sec.)
>150% (Immediate)
>150% (Immediate)
>150% (Immediate)
>150% (Immediate)
Short Circuit Capability
90A
90A*
90A*
160A*
Power Module Circuit Breaker
20A (2 pole)
40A
40A
63A
Transformer Module* Circuit Breaker
Four 20A (single pole)
30A (3 pole)
30A (3 pole)
63A (3 pole)
Crest Factor
3:1
3:1
3:1
3:1
* The short circuit capability at 1ø 2W 120V for the SU6000RT3U and SU6000RT3UXR is greater than 180A, and for the SU10KRT3U is greater than 320A.
Operation
On-Line Transfer Time
(Line to Battery, Battery to Line)
0 ms.
0 ms
0 ms
0 ms
Audible Noise (Full Load @ 1 m)
<50 dBA
<50 dBA
<55 dBA
<55 dBA
Indicators
Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).
Communications
Includes an RS-232 DB9 female connector, a dry contact DB9 female connector and an accessory slot.
Physical Specifications
Unit Dimensions (H x W x D)
Power Module
5.25 (3U) x 17.5 x 26 in.
5.25 (3U) x 17.5 x 22.5 in.
5.25 (3U) x 17.5 x 22.5 in.
5.25 (3U) x 17.5 x 22.5 in.
[13.4 x 44.5 x 66 cm.]
[13.4 x 44.5 x 57.2 cm.]
[13.4 x 44.5 x 57.2 cm.]
[13.4 x 44.5 x 57.2 cm.]
Transformer Module*
3.5 (2U) x 17.5 x 20.75 in.
5.25 (3U) x 17.5 x 26 in.
5.25 (3U) x 17.5 x 26 in.
5.25 (3U) x 17.5 x 26 in.
[8.9 x 44.5 x 52.7 cm.]
[13.4 x 44.5 x 66.1 cm.]
[13.4 x 44.5 x 66.1 cm.]
[13.4 x 44.5 x 66.1 cm.]
Battery Module #1
3.5 (2U) x 17.5 x 22.50 in.
5.25 (3U) x 17.5 x 22.5 in.
5.25 (3U) x 17.5 x 22.5 in.
5.25 (3U) x 17.5 x 22.5 in.
[8.9 x 44.5 x 52.7 cm.]
[13.4 x 44.5 x 57.2 cm.]
[13.4 x 44.5 x 57.2 cm.]
[13.4 x 44.5 x 57.2 cm.]
Battery Module #2 (if applicable)
N/A
N/A
5.25 (3U) x 17.5 x 22.5 in.
N/A
[13.4 x 44.5 x 57.2 cm.]
Shipping Weight
Power Module
58 lb. [27 kg.]
58 lb. [27 kg.]
58 lb. [27 kg.]
68 lb. [31 kg.]
Transformer Module*
60 lb. [28 kg.]
124 lb. [57 kg.]
124 lb. [57 kg.]
124 lb. [57 kg.]
Battery Module #1
138 lb. [63 kg.]
160 lb. [73 kg.]
160 lb. [73 kg.]
160 lb. [73 kg.]
Battery Module #2 (if applicable)
N/A
N/A
160 lb. [73 kg.]
N/A
* Transformer Module not included with hardwire (HV) models.
Optional corded backplate outlet kits available: SUPDM11
(SU6000RT3UHV); SUPDM12 (SU6000RT3U & SU6000RT3UXR);
SUPDM13 (SU6000RT3U & SU6000RT3UXR); SUPDM15
(SU6000RT3U & SU6000RT3UXR); SUPDM16 (SU6000RT3U
and SU6000RT3UXR)