beautypg.com

Connection, Continued – Tripp Lite 5kVA User Manual

Page 13

background image

13

Connection Combination #3:
Power Module (either 6kVA or 10kVA) + Battery Module(s)

Hardwire the power module to your equipment.

Using a screwdriver, remove the top of the box

covering the power module’s

input and output terminals. Pass a user-supplied cable through the terminal
box’s left knockout

and connect it to the power module’s output terminals.

Connect the other end of the cable to your equipment.

Hardwire the power module to a utility power source.

Pass a user-supplied cable through the box’s right knockout

and connect it

to the power module’s input terminals. Replace the top of the terminal box.
Connect the other end of the cable to a utility power source.

Connect the battery module to the power module.

Consult the owner’s manual that came with your battery module. Fully insert
the connector on the end of the battery module’s cable

into the connector

on the rear panel of the power module

. Small sparks may occur; this is nor-

mal. NOTE: the power module does not contain internal batteries and will not
start until a battery module is connected. The battery modules are fully charged
prior to shipping. However, before expecting full backup capability (particularly
if the battery module has been stored for an extended period) after the UPS system
is connected to a utility power source, allow the battery module to recharge for
12 hours. Once the UPS system is in use, it will charge the batteries and maintain
the charge level automatically. If needed, connect additional battery modules
in a daisy-chain with each module’s cable inserted into the previous module’s
connector

.

F

E

D

C

B

A

1

2

2

3

3

A

B

C

D

E

F

1

6kVA Power Module Shown

Connection