TD - Series

- 17 -

TD Series

Digital Solid State Soft Starter 48 - 1250A

5.4 The TD Function List

5.4.1 Motor FLA, Service Factor and Overload Protection Functions

5.4.2 Starting Mode Functions

5.4.3 Jog Mode Functions

Note 1: Current percentages are based on Motor Full Load Amps (FLA) as entered in F001.

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F001

Motor Nameplate FLA
Motor FLA must be programmed
for proper unit operation.

50-100% of starter Max. Amp rating
Upper limit of range automatically
adjusts downward as Service
Factor is increased

1 amp

0

(Starter disabled

until set to FLA)

5.5.1

F002

Motor Nameplate Service Factor

1.00 - 1.30

0.05

1.0 SF

5.5.1

F003

Overload Class During Start

5 - 30 NEMA / UL Class
Overload Time / Trip Curve

5

Class 10

5.5.1

F004

Overload Class During Run

5 - 30 NEMA / UL Class
Overload Time / Trip Curve

5

Class 10

5.5.1

F005

Overload Reset

0=Manual
1=Auto
2=Disabled Overload

1

0 (Manual)

5.5.1

5.5.1

F006-

F009

Reserved

Reserved

Reserved

Reserved

Motor

and O

verl

oad

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F010

Ramp Select

VR = Voltage Ramp,
CR = Current Ramp

Range is 1 - 4
Setting to #1: Ramp 1 = VR, Ramp 2 = VR
Setting to #2: Ramp 1 = CR, Ramp 2 = CR
Setting to #3: Ramp 1 = VR, Ramp 2 = CR
Setting to #4: Ramp 1 = CR, Ramp 2 = VR

1

1 (VR1-VR2)

5.5.2

F011

Initial Voltage of Ramp 1

0-100%

1%

60%

5.5.2

F012

Initial Current of Ramp 1

0-600% (note1)

1%

200%

5.5.2

F013

Accel Ramp Time of Ramp 1

1-120 seconds

1 second

10 seconds

5.5.2

F014

Max Current Limit of Ramp 1

200 - 600% (note1)

1%

350%

5.5.2

F015

Initial Voltage of Ramp 2

0-100%

1%

60%

5.5.2

F016

Initial Current of Ramp 2

0-600% (note1)

1%

200%

5.5.2

F017

Accel Ramp Time of Ramp 2

1-120 seconds

1 second

10 seconds

5.5.2

F018

Max Current Limit of Ramp 2

200 - 600% (note1)

1%

350%

5.5.2

S

tart

ing

Mode

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F019

Voltage Jog

5 - 100%

1%

50%

5.5.3

F020

Time of Voltage Jog

1 - 20 Seconds

1 second

10 seconds

5.5.3

F021

Current Jog

100 - 500%

1%

150%

5.5.3

Jog

Mod