beautypg.com

5 mounting and cleaning, 6 power terminal wire range and tightening torque – Toshiba 48-1250 A User Manual

Page 11

background image

TD - Series

- 5 -

TD Series

Digital Solid State Soft Starter 48 - 1250A

2.5 Mounting and Cleaning

When drilling or punching holes in the enclosure, cover the electrical assembly
to prevent metal filings from becoming lodged in areas which can cause
clearance reduction or actually short out electronics. After work is complete,
thoroughly clean the area and reinspect the unit for foreign material. Make
sure there is sufficient clearance (six inches) all around the unit for cooling,
wiring and maintenance purposes. To maximize effective air flow and cooling,
the unit must be installed with its heat sink ribs oriented vertically and running
parallel to the mounting surface.

Remove all sources of power before cleaning the unit.

In dirty or contaminated atmospheres the unit should be cleaned on a regular
basis to ensure proper cooling. Do not use any chemicals to clean the unit.
To remove surface dust use 80 to 100 psi, clean, dry compressed air only. A
three inch, high quality, dry paint brush is helpful to loosen up the dust prior
to using compressed air on the unit.

2.6 Power Terminal Wire Range and Tightening Torque

Note: All wiring must be sized according to NEC standards.

WARNING

Model Number

Wire range

Torque lbs/in

TD005

#18 - #4

20

TD006

#14 - #2

50

TD007

TD008

TD009

TD010

TD011

TD012

TD013

TD014

TD015

TD016

TD017

#6 - 250 kcmil

325

375

(3) #2 - 600 kcmil

375

(2) #2 - 600 kcmil

375

(2) #2 - 600 kcmil

(4) #2 - 600 kcmil

375