Toshiba 48-1250 A User Manual

Page 18

background image

TD - Series

- 12 -

TD Series

Digital Solid State Soft Starter 48 - 1250A

4.2.6 Fault Signal

An optical AC switch triac driver is used for fault indication. This signal energizes
with the fault LED. The optical output is rated for 240 VAC, 50 mA (maximum).

4.2.7 Resetting Faults

To reset faults, press the RESET key on the keypad.

4.2.8 Enabling the Jog Function

Closing TB4 Pins 1 and 2 will enable the Jog feature. The Jog feature can be
used for tasks such as lining up machines for blade or bit changes or inching
belts along to check tracking. See chapter 9 for main control board layout.

4.2.9 Enabling the Dual Ramp Feature

Closing TB4 Pins 1 and 3 will enable ramp 2. The dual ramp feature is useful in
instances where a load changes such as a loaded or unloaded conveyor belt.
The characteristics for starting an unloaded conveyor can be programmed for
ramp 1. The characteristics for starting a loaded conveyor can be programmed
for ramp 2.

4.3 Interlock Connection

TB1 provides a connection point for an external user N.C. (normally closed)
interlock device between pins 2 and 3. (Examples of the use of this interlock
connection would be for conditions such as low oil, high temperature, or excess
vibration from user supplied devices).
A factory installed jumper is provided which allows the TD unit to operate if
external interlocks are not used. If this jumper is removed and an interlock is not
used, the TD unit will not function.

1 2 3

TB4

Common

Dual

Ramp

1 2 3

TB4

Common

Jog

1

2

3

4

5

6

TB1

Interlock

1

2

3

4

5

6

7

8

9

10

C

NO

NC

C

NO

NC

C

NO

NC

TB2

240Vac

50mA

240Vac / 5A / 1200VA

AUX 3

Fn F051

Fn F052

Optical Triac

Driver

AUX 1

Fn F050

AUX 2

11

12

Programmable

Relay

Programmable

Programmable

Relay

Relay

Fault

Signal