1800 Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 3.0 August 2008
2.4 kVA

Page 6 of 6

12.0 Environment

Operation


Operating Ambient Temperature:

0 ~ 40

o

C (32 ~ 104

o

F)


Recommended

Temperature:

+15

o

C ~ 25

o

C


Storage

Temperature:

-20

o

C ~ 40

o

C


Humidity:

30-90%,

Non-Condensing


Audible Noise:

50dB (A) maximum @ 1 meter from Front Panel


Altitude:

1000 m (3,000 ft) above sea level


13.0 Conformance

UL 1778, CUL, CE, FCC Part 15 Class A


14.0 Warranty

Toshiba Standard warranty includes 3 Years of on site service which covers electronics
and labor, and a 5 year warranty on the batteries (2 years full, 3 years pro-rated)


15.0 Options

15.1

Remote

Monitoring

The UPS contains a communication slot this allows the operator to field install an
optional RemotEye II card. The RemotEye II card allows the UPS to communicate via
Ethernet SNMP, connected directly to the Local Area Network. SNMP/ Web based
monitoring – Toshiba UPS system provides comprehensive monitoring of the UPS
operation. The optional RemotEye II features an HTTP (web-based) interface for
Toshiba UPS. This allows easy access to the Toshiba UPS information from any
PC/Network with a web browser.


15.2

Environmental Monitoring Device (EMD)
The EMD is an environmental monitoring device that provides remote monitoring of
temperature, humidity and other environmental conditions via standard web browser or
network management systems. The EMD provides automated events notification when
temperature, humidity or user defined dry contacts is out of configured tolerance.