1800 Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 3.0 August 2008
2.4 kVA

Page 3 of 6

6.0 UPS

Output

Voltage:

208/240 VAC Single Phase


Capacity:

kVA

kW

(@

0.70PF)

2.4

kVA

(208/240V)

1596W


Regulation:

+/-3%

(with

AC

power and during battery backup)


Distortion:

Less than 3% THD at full Linear Load


Step Load:

± 9 % max from 100% to 0 % or from 0% to 100 % linear load


Output

Current:

kVA

RMS

PEAK

2.4

(240V)

9.5A

23.75A


Overload Capacity (Inverter):

150% for 30 seconds

125%

for

60

seconds

Crest Factor:

2.5 at Full Load


Frequency:

50/60Hz

Auto

Sensing


Regulation:

±

0.5Hz


Synchronous

Range:

+/-

1

Hz


Wave Form:

Sine wave, Zero Transfer Time


Load Power Factor:

0.7 lagging


Efficiency AC to AC: Greater than 79% (208/240V)

Noise Isolation: Neutral is bonded to ground on the output of the Isolation transformer

for isolation of common mode

Bypass:

Manual bypass provided with switch with less than 4 ms transfer


7.0 UPS

Battery

Battery Bus Volts:

48 VDC nominal

Backup

time:

7

minutes


Type of Battery:

Enersys NPX-35 Flame Retardant Lead Acid 9Ah/12V


Number of Battery:

2 Strings in Parallel, 4 batteries per String


Average Recharge:

9 hours (3.5 hours for 90%)


Cutoff Voltage: 1.6 Volts per cell