Toshiba RAV-SM1101BT-E User Manual
Page 63
61
NO
NO
NO
NO
NO
YES
YES
NO
YES
YES
YES
NO
YES
YES
NO
YES
Correct connection of connector.
Replace TCJ sensor.
Improve the power supply line.
Replace IPDU.
Check indoor P.C. board
(MCC-1402).
Defect
Replace
Is connection of TCJ sensor connector
(Indoor P.C. board CN102) normal?
Are characteristics of
TCJ sensor resistance value normal?
* Refer to Characteristics-2.
* For RAV-SM560AT-E,
check RY01 on the control P.C. board.
* Single-phase type is not
provided to RAV-SM560AT-E.
* Replace control P.C. board
of RAV-SM560AT-E.
Is power voltage normal?
Is not AC fuse fused?
Check and correct circuit cables.
Correct connection of connector.
Check and correct reactor connection.
Are connections of
cabling/connector normal?
Does RY01 relay of
IPDU operate?
Are not “P26” and “14” errors output
when an operation is performed by
removing 3P connector of compressor?
Replace IPDU.
* Replace control P.C. board
of RAV-SM560AT-E.
Is compressor normal?
Check rare short of compressor trouble.
Defect
Replace
Check IPDU.
Defect
Replace
[F01 error]/[0F error]
[P26 error]/[14 error]