11. Defrost control



In heating operation, defrost operation is performed when TE sensor temperature satisfies any

condition in A zone to D zone.

‚

The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or

it also is finished when condition of 7°C

TE < 12°C has continued for 1 minute. The defrost operation

is also finished when defrost operation has continued for 10 minutes even if TE sensor temperature
has become 7°C or lower.

ƒ

After defrost operation has finished, the compressor and the outdoor fan start heating operation after

stopped for approx. 50 seconds.

Start of heating operation

a

b

c

d

T

SM560

28

28

28

60

120

A zone

B zone

C zone

D zone

Defrost operation is performed in this zone when TE0-TE

3 continued for T seconds.

Defrost operation is performed in this zone when TE0-TE

3 continued for T seconds.

Defrost operation is performed when this zone continued for T seconds.

Defrost operation is performed when this zone continued for T seconds.

0

10

15

c

b

a

d

[min]

*

TE [˚C]

–5

–10
–13

–18

A z

A zone

one

B z

B zone

one

C z

C zone

one

D z

D zone

one

A zone

B zone

C zone

D zone

* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in memory as TE0.

SM800, SM1100, SM1400

34

40

55

90

20