beautypg.com

Toshiba RAV-SM1101BT-E User Manual

Page 60

background image

58

Correct connection of connector.

Replace indoor fan motor.

*

1

• Are not coil windings between

(Red lead) and (White lead),

between

(White lead) and (Black lead), between

(Black lead) and (Red lead) opened or shorted?

For resistance, see the following values.

SM560, SM800, SM1100

Approx. 70 to 100

SM1400

Approx. 35 to 60

• Is not earthed between cabinet and 1, 3, 5

10M or more

*

2

Check resistance of fan motor position detection circuit.
Is not coil winding between (Yellow lead) and (Pink lead)
opened or shorted?

Resistance: Approx. 5 to 20k

*

3

Check fan motor position detection signal.
• Using a tester, measure the voltage between CN334 and of

indoor P.C. board (MCC-1402) under condition that CN333 and
CN334 are mounted and the power is turned on.

Rotate the fan slowly with hands,

and check the pin voltage
swings between 0 to 5V voltage.

• Between and : 5V

Check indoor P.C. board
(MCC-1402).
Defect

Replace

Remove connectors CN333 and
CN334 of indoor unit P.C. board
(MCC-1402).

Replace indoor fan motor.

Replace indoor fan motor.

Replace indoor fan motor.

YES

NO

NO

NO

NO

NO

YES

YES

YES

YES

Turn off the power.

Is resistance value of fan motor connector

CN333 at motor side of indoor P.C. board

(MCC-1402) correct? *2

Are not there connections errors or

disconnection on connectors CN333 and CN334

of indoor unit P.C. board (MCC-1402)?

Are resistance values between phases

at fan motor connector CN333 motor side of

indoor P.C. board (MCC-1402) correct? *1

Is signal output of indoor fan motor

position detection correct? *3

Does the fan rotate without trouble

when handling the fan with hands?

1

3

3

5

5

1

1

5

4

5

4

1

CN333

CN334

[P12 error]/[11 error]

This manual is related to the following products: