4. Outdoor fan control (Object: SM800, SM1100, SM1400)

Allocautions of fan tap revolutions [rpm]

TO

MIN

MAX

TO < 5°C

5

TO <10°C 10

TO < 15°C 15

TO < 20°C 20

TO < 25°C

25°C

TO

TO error

W1

W2

W3

W4

W5

WA

W1

W6

W8

WA

WC

WE

WE

WE

2) Heating fan control



This control function lowers fan tap according to

TE sensor value when outdoor temperature is
high.

‚

When a status TE > 20°C is detected continu-
ously for 5 minutes, the operation may stop. This
status does not output an error code and is
assumed as usual status of thermo-OFF. The fan
restarts after approx. 2 minutes 30 seconds and
this intermittent operation is not a trouble.

ƒ

If the status in item

‚

is frequently found, it is

considered that the filter of suction part of the
indoor unit is dirty. Clean the filter and restart the
operation.

„

This control function does not work for 30 min-
utes after activation, 1 minute after defrosting,
and during defrost operation.

Control for fan tap by outdoor temperature in normal operation

1) Cooling fan control



The outdoor fan is controlled by TE sensor.
(Cooling: Temperature conditions after medium
term)

The cooling fan is controlled by every 1 tap of DC
fan control (14 taps).

‚

At the activation time, although the maximum fan
tap in the following table are fixed for 60 seconds,
after then the fan may not rotate with high speed
for several minutes because the fan is controlled
by TE sensor value. It is not an abnormal status.

ƒ

When the discharge temperature sensor is
abnormal or the sensor comes off the holder, the
fan does not rotate with high speed, but a protec-
tive device works.

„

When the outdoor fan does not rotate with high
speed, judge a fan error by comparing the control
data in the following table with TO and TE values.

MAX.

+30 rpm / 20 sec.

Hold zone

–30 rpm / 20 sec.

MIN.

46

37

34

20

TE [˚C]

–60 rpm / 20 sec. STOP timer count

–60 rpm / 20 sec.

–30 rpm / 20 sec.

Hold zone

+30 rpm / 20 sec.

24

21

17

15

TE [˚C]

SM800

SM1100

SM1400

Upper fan

Lower fan

Upper fan

Lower fan

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

250

270

290

310

340

370

400

440

480

520

560

610

700

780

250

280

300

320

340

380

420

470

520

570

630

690

740

800

OFF

OFF

270

290

400

480

520

560

600

660

720

780

860

940

250

270

270

300

350

410

470

530

590

670

750

810

840

860

OFF

OFF

240

270

330

390

450

510

570

650

730

790

820

840