Diagnostics – Trane CGWN 205-211 User Manual
Page 30

Diagnostics
CG-SVU02B-E4
30
Comm Loss:
Suction Pressure Transducer
Circuit
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Ext Chilled/Hot Wtr Setpoint
Chiller
Warning
and Special
Action
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Chilled/Hot Water
Setpoint source and revert to the next higher priority for
setpoint arbitration
Remote
Comm Loss:
External Demand Limit
Setpoint
Chiller
Warning
and Special
Action
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Demand Limit Setpoint
source and revert to the next higher priority for setpoint
arbitration
Remote
Comm Loss:
Auxiliary Setpoint Command
Chiller
Warning
and Special
Action
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the Auxiliary Setpoint and revert to the
Chilled Water Setpoint based on setpoint arbitration
Remote
Comm Loss:
High Pressure Cutout Switch
Chiller
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Evaporator Water Flow Switch
Chiller
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Condenser Water Flow Switch
Chiller
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Local BAS Interface
Chiller
Warning
and Special
Action
NonLatch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Use the
last values sent from BAS
Remote
Comm Loss:
Solenoid Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Motor Temp/Overload
Cprsr
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Compressor Run Command
Cprsr
Immediate
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Protection Module Cprsr
Circuit
Warning
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote