DynaView Interface
15
CG-SVU02B-E4
Circuit Level Mode
Top Level Mode
Description
Running - Limit
The compressor on the given circuit is currently running in a
limit mode.
Running - Limit Sub Modes
Description
Hot Start Limit
Additional stages on a given circuit are being held off based
on leaving evaporator temperature.
Condenser Pressure Limit
The circuit is being inhibited from loading due to high
condenser pressure.
Low Evaporator Pressure Limit
The circuit is being inhibited from loading due to low
evaporator pressure.
Circuit Level Mode
Top Level Mode
Description
Preparing Shutdown
The circuit is preparing to de-energize the compressor.
Preparing Shutdown Sub Modes
Description
Operational Pumpdown
The operational pumpdown is enabled and the circuit is
shutting down.
Circuit Level Mode
Top Level Mode
Description
Shutting Down
The chiller is going through the necessary steps after de-
energizing the compressor.
Shutting Down Sub Modes
Description
No Circuit Sub-Modes
Circuit Level Mode
Top Level Mode
Description
Misc.
These sub modes may be displayed in most of the top level
circuit modes
Misc. Sub Modes
Description
Defrosting
The circuit is in a defrost operational mode.
Service Pumpdown
The circuit is currently performing a service pumpdown.
Compressor X Running
A specific compressor is running where X is A or B.
Restart Time Inhibit Cprsr X: MIN:SEC
If there is accumulated Restart Inhibit Time, it must expire
before the compressor is allowed to start. X is denoted as
compressor A or B.