DynaView Interface
CG-SVU02B-E4
10
Table 1 - Main screen menu, Chiller Operating Modes - Top Level
Chiller Level Mode
Top Level Mode
Description
MP Resetting
The main processor is going through reset.
MP Resetting Sub Modes
Description
No Chiller Sub-Modes
Chiller Level Mode
Top Level Mode
Description
Stopped
The chiller is not running either circuit, and cannot run without
intervention.
Stopped Sub Modes
Description
Local Stop
Chiller is stopped by the DynaView Stop button command-
cannot be remotely overridden.
Immediate Stop
Chiller is stopped by the DynaView Immediate Stop (by
pressing the Stop then Immediate Stop buttons in
succession) - previous shutdown was manually commanded
to shutdown immediately.
No Circuits Available
The entire chiller is stopped by circuit diagnostics or lockouts
that may automatically clear.
Diagnostic Shutdown - Manual Reset
The chiller is stopped by a diagnostic that requires manual
intervention to reset.