Diagnostics

25

CG-SVU02B-E4

Table 5 - Main Processor Diagnostics

Diagnostic Name

Effects

Severity

Persistence

Active

Modes

[Inactive

Modes]

Criteria

Reset

Level

MP: Reset Has Occurred

Chiller

Warning

NonLatch

All

The main processor has successfully come out of a reset and
built its application. A reset may have been due to a power up,
installing new software or configuration. This diagnostic is
immediately and automatically cleared and thus can only be
seen in the historic diagnostic list.

NA

Low Pressure Cutout

Circuit

Immediate

Latch

Starting and

Running

[Stop, See

criteria]

The suction refrigerant pressure (gauge) fell below the given
threshold for the refrigerant installed:
• 0.7 bar for R22 and R407c
• 0.3 bar for R134a
• 1.0 bar for R410a

Local

High Motor Temp/Overload

Cprsr

Immediate

Latch

All

• The High Motor Temperature or the Compressor Overload
switch remained open for more than 35 minutes.
• Five compressor fault diagnostics have occurred within the
last 210 minutes.

Local

Compressor Fault

Cprsr

Immediate

NonLatch

All

The High Motor Temperature or the Compressor Overload
switch input is open.

Local

BAS Failed to Establish
Communication

Chiller

Special

NonLatch

At power-up The BAS was setup as "installed" and the BAS did not

communicate with the MP within 15 minutes after power-up.

Remote

BAS Communication Lost

Chiller

Special

NonLatch

All

The BAS was setup as "installed" at the MP and the Comm
3 LLID lost communications with the BAS for 15 continuous
minutes after it had been established. The chiller follows the
value of the Tracer Default Run Command which can be
previously written by Tracer and stored nonvolatilely by the MP
(either use local or shutdown).

Remote

External Chilled/Hot Water
Setpoint

Chiller

Warning

NonLatch

All

a. Function Not "Enabled": no diagnostics.
b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set
diagnostic, default CWS/HWS to next level of priority (e.g.
Front Panel SetPoint). This Warning diagnostic will automatically
reset if the input returns to the normal range.

Remote

External Demand Limit
Setpoint

Chiller

Warning

NonLatch

All

a. Function Not "Enabled": no diagnostics.
b. "Enabled ": Out-Of-Range Low or Hi or bad LLID, set
diagnostic, default DLS to next level of priority (e.g. Front Panel
SetPoint). This Warning diagnostic will automatically reset if the
input returns to the normal range.

Remote

Circuit Pumpdown
Terminated

Circuit

Warning

Latch

Operational/

Service

Pumpdown

[All Except

Operational

and Service

Pumpdown]

Going below the low pressure setting + 0.2 bar shall terminate
Service Pumpdown. This indicates that the suction pressure of
circuit 1 or 2 did not go below the low pressure setting + 0.2
bar within 1 minute from the start of Service Pumpdown.

Remote

Chilled Water Flow (Entering
Water Temp)

Chiller

Immediate

Latch

Any Ckt(s)

Energized
[No Ckt(s)

Energized]

The entering evaporator water temperature fell below the
leaving evaporator water temperature by more than 1.7°C for
37°C sec while at least 1 compressor was running.

Remote