Operation, Bypass messages, Overload messages – Tripp Lite Modular UPS Systems SU16000RT4U User Manual

Page 13

background image

13

Operation

(continued)

The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to BYPASS
MODE to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:

Overload Condition

Countdown Duration

102% - 125%

1 minute

125% - 150%

30 seconds

> 150%

Immediate Bypass

Bypass Messages

While in BYPASS MODE, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not
provide battery backup in BYPASS MODE. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than
nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level,
the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned
to nominal.

Bypass Voltage Conditions

L1 > 15% Higher

Than Nominal Voltage

L2 > 15% Higher

Than Nominal Voltage

L1 > 20% Lower

Than Nominal Voltage

L2 > 20% Lower

Than Nominal Voltage

L1 Voltage Was Too High,

Now Returned to Nominal Voltage

L2 Voltage Was Too High,

Now Returned to Nominal Voltage

L1 Voltage Was Too Low,

Now Returned to Nominal Voltage

L2 Voltage Was Too Low,

Now Returned to Nominal Voltage

BYPASS AC1 HIGH

LOAD1 = XXX% X.XKW

LCD Screen Messages

BYPASS AC2 HIGH

LOAD1 = XXX% X.XKW

BYPASS AC1 LOW

LOAD1 = XXX% X.XKW

BYPASS AC2 LOW

LOAD1 = XXX% X.XKW

BYPASS AC1 WAS HI

LOAD1 = XXX% X.XKW

BYPASS AC2 WAS HI

LOAD1 = XXX% X.XKW

BYPASS AC1 WAS LO

LOAD1 = XXX% X.XKW

BYPASS AC2 WAS LO

LOAD1 = XXX% X.XKW

OVERLOAD!

LOAD1 = XXX% X.XKW

OVERLOAD!

LOAD2 = XXX% X.XKW

Overload Messages

When the UPS detects an output overload, its LCD will switch to the following display: