Before test run
• Before turning on the circuit breaker, carry out the
following procedure.
1) Using 500V-megger, check 1M
Ω or more exists
between the terminal block L
1
to L
2
and the
ground.
If 1M
Ω or less is detected, do not run the unit. Do
not apply to the remote control circuit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more be for operating.
Execute a test run
Using the remote control, operate the unit as usual.
For the procedure of the operation, refer to the
attached Owner’s Manual.
A forced test run can be executed in the following
procedure even if the operation stops by thermo.-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
• Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
Wired remote control
Procedure
1
Keep
button pushed for 4 seconds or more. [TEST]
is displayed on the display part and the selection of
mode in the test mode is permitted.
Procedure
2
Push
button.
Procedure
3
Using
button, select the operation mode,
[COOL] or [HEAT].
• Do not run the air conditioner in a mode other than
[COOL] or [HEAT].
• The temperature controlling function does not work
during test run.
• The detection of error is performed as usual.
Procedure
4
After the test run, push
button to stop a test
run.
(Display part is same as procedure 1.)
Procedure
5
Push
check button to cancel (release from) the test
run mode.
([TEST] disappears on the display and the status
returns to a normal.)