beautypg.com

Toshiba CARRIER RAV-SP420CT-UL User Manual

Page 14

background image

– 13 –

Under Ceiling Type

Installation Manual

Toshiba

Thermal insulation process

Apply thermal insulation for the pipes separately at
liquid side and gas side.
For the thermal insulation to the pipes at gas side, be
sure to use the material with heat-resisting
temperature 248 °F (120 °C) or higher.
Using the attached thermal insulation material, apply
the thermal insulation to the pipe connecting section of
the indoor unit securely without gap.

REQUIREMENT

• Apply the thermal insulation to the pipe connecting

section of the indoor unit securely up to the root
without exposure of the pipe. (The pipe exposed to
the outside causes water leak.)

• Wrap heat insulator with its slits facing up (ceiling

side).

Indoor unit

Union

Heat insulation

pipe

(Accessory)

Flare nut

Heat insulator

of the pipe

Wrap the pipe with the attached heat insulator

without any gap between the indoor unit.

The seam must be faced upward

(ceiling side).

13-EN

+00EH99864801_00Ta.book Page 13 Tuesday, November 24, 2009 5:40 PM