Installation of hanging bolts, Draw-out direction of pipe/ wire, Pipe knockout hole – Toshiba CARRIER RAV-SP420CT-UL User Manual

Page 10

background image

– 9 –

Under Ceiling Type

Installation Manual

Toshiba

Using attached installation pattern

Using the pattern, positioning of the hanging bolt and
pipe hole can be performed.
* As an error to some degree may generate on the

pattern size due to temperature and humidity, be

sure to confirm the size.

„

Installation of hanging bolts

Use 3/8” (M10) hanging bolts (4 pcs, to be local
procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.

„

Draw-out direction of pipe/
wire

• Decide installation place of the unit and draw-out

direction of pipe and wire.

„

Pipe knockout hole

• Piping from rear side

* Cut off the groove section with a plastic cutter, etc.

• Piping from right side

* Cut off the groove section with a metal saw or

plastic cutter, etc.

• Piping from left side

Taking pipe from left side is applied only to the
drain pipe.
The refrigerant pipe cannot be taken out from the
left side.
* Cut off the groove section with a metal saw or

plastic cutter, etc.

Piping from upper side

Taking pipe from upper side is applied only to
the refrigerant pipe.
When taking out the drain pipe from the upper
side, use a drain up kit sold separately.
Open the upper pipe draw-out port (Knockout hole)
shown in the external view.
(Knockout hole of thin plate)
After piping, cut off the attached thermal insulator of
the top plate to pipe shape, and then seal the
knockout hole.

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel flame structure

Use existing angles or install new support angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Ceiling surface
Wall face

Installation pattern

Rubber

Anchor bolt

(Blade type

bracket)

(Slide type

bracket)

(Pipe hanging

anchor bolt)

Hanging bolt

Hanging bolt Support angle

100

Rear cover

Opened when

refrigerant pipe is

taken out from the

rear side

Grooves

Opened when only drain pipe is

taken out from the rear side

Groove

Side panel (Right side)

Groove

Side panel (Left side)

9-EN