Remote control switch monitoring function – Toshiba CARRIER RAV-SP420CT-UL User Manual

Page 27

background image

– 26 –

Under Ceiling Type

Installation Manual

EN

Toshiba

„

Remote control switch
monitoring function

This function is available to call the service monitor
mode from the remote control during a test run to
acquire temperatures of sensors of the remote control,
indoor unit, and outdoor unit.
1. Push

and

buttons simultaneously for at least

4 seconds to call the service monitor mode.
The service monitor indicator lights up and the
header indoor unit number is displayed first. CODE
No.

is also displayed.

2. Pushing TEMP.

buttons, select the

number of sensor, etc. (CODE No.) to be monitored.
(See the following table.)

3. Pushing

(left side of the button), select an

indoor unit to be monitored. The sensor
temperatures of indoor units and their outdoor unit in
the control group are displayed.

4. Push

button to return to the normal display.

Indoor unit data

CODE No.

Data name

01

Room temperature (remote control)

02

Indoor unit intake air temperature (TA)

03

Indoor unit heat exchanger temperature

(TCJ)

04

Indoor unit heat exchanger temperature

(TC)

F3

Indoor unit fan cumulative operating hours

(x1 h)

F8

Indoor unit discharge air temperature

1

3

4

2

Outdoor unit data

CODE No.

Data name

60

Outdoor unit heat exchanger temperature

(TE)

61

Outside air temperature (TO)

62

Compressor discharge air temperature (TD)

63

Compressor intake air temperature (TS)

64

65

Heatsink temperature (THS)

6A

Operating current (x1/10)

F1

Compressor cumulative operating hours

(x100h)

26-EN