– 14 –

Under Ceiling Type

Installation Manual

EN

Toshiba

5

DRAIN PIPING WORK

CAUTION

Following the Installation Manual, perform the

drain piping work so that water is properly
drained, and apply a heat insulation so as not to
cause a dew dropping.
Inappropriate piping work may result in water
leakage in the room and wet of furniture.

„

Piping/Heat insulating
material

Require the following materials for piping and heat
insulating at site.

REQUIREMENT

• Be sure to perform heat insulation of the drain pipes

of the indoor unit.

• Never forget to perform heat insulation of the connecting

part with the indoor unit.
An incomplete heat insulation causes dew dropping.

• Set the drain pipe with downward slope (1/100 or

more), and do not make swelling or trap on the
piping. It may cause an abnormal sound.

• For length of the traversing drain pipe, restrict 65’7”

(20 m) or less.
In case of a long pipe, provide support brackets with
interval of 4’11” - 6’7” (1.5 - 2 m) in order to prevent
waving.

• Set the collective piping as shown in the below

figure.

• Be sure not to apply force to the connecting part of

the drain pipe.

• The hard vinyl-chloride pipe cannot be directly

connected to the drain pipe connecting port of the
indoor unit.
For connection with the drain pipe connecting port,
be sure to use/fix the attached flexible hose with the
hose band, otherwise a damage or water leak is
caused on the drain pipe connecting port.

Adhesive inhibited:
Use the attached flexible hose and hose band for
connecting the drain hose to the clear drain socket.
If applying the adhesive, socket will be damaged and
cause water leakage.

„

Drain up

When not securing down slope on the drain pipe, use
a Drain pump kit sold separately.
Also refer to the “Drain pump kit installation manual”.
The drain pipe can be raised 23.6” (600 mm) from the
top face of the main unit.
* When using Drain pump kit, both drain pipe and

refrigerant pipe can be taken only from upper side.

* VP25 PVC pipe is needed when a drain pump is

used.

Piping

Hard vinyl chloride pipe VP20

(Outer dia.: Ø1.0” (26 mm))

Heat insulator

Foam polyethylene:

Thickness 0.4” (10 mm) or more

Support

bracket

Thermal insulator

NO

GOOD

4’11” - 6’7” (1.5 - 2 m)

1/100 or more

downward

Arched shape

Trap

VP20

As long as possible

(3.9” (100 mm))

Downward slope

1/100 or more

VP30 or more

VP20

VP20

Extended

ventilating

pipe

Drain pipe connecting

port (Hard socket)

Attached flexible hose

VP20 vinyl chloride pipe

(procured locally)

Soft socket

Soft socket

Adhesive agent

prohibited

Attached hose band

Attached hose band

Drain pan