Specifications—hardwired models – Tripp Lite APS 912 INT ES User Manual
Page 15
![background image](/manuals/211171/15/background.png)
15
APS 2424 INT
2400W
4800W
89%
220A
112A
1.8A*
24 VDC
20-30 VDC
230 VAC ± 5%
50 Hz
30A
Selectable:
28.8V/28.4V Wet/Gel
26.6V Wet/27.2V Gel
230V
8.5A
Selectable:
144**, 163, 182, or 201VAC
Selectable: 259** or 264 VAC
19.1A
45-55 Hz
10.4A
4-6 ms
Specifications—Hardwired Models
HARDWIRED MODELS:
APS 2012 INT
Weight:
17.1 Kg
18.5 Kg
INVERTER
Continuous power (@ 20° C):
2000W
Surge power (5 seconds):
4000W
Efficiency (Full Load):
89%
Minimum DC Fuse Rating:
370A
DC Input Current @ Nominal V DC
Full Load :
187A
No Load :
3A*
Nominal DC Input:
12 VDC
DC Input Voltage Range:
10-15 VDC
Nominal Output Volts:
230 VAC ± 5%
Nominal Output Frequency:
50 Hz
BATTERY CHARGER
Charging Capacity DC:
60A
Acceptance Volts VDC:
Selectable
14.4V/14.2V Wet/Gel
Float Volts VDC:
13.3V Wet/13.6V Gel
Input Voltage AC:
230V
Input Current AC:
8.5A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable:
144**, 163, 182, or 201VAC
Maximum Input AC Volts:
Selectable: 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
17.4A
Input Frequency:
45-55 Hz
Maximum Output AC (Continuous):
8.7A
Automatic Transfer Time:
4-6 ms
HARDWIRED MODELS:
APS 3636 VRI
Weight:
25.6 Kg
INVERTER
Continuous power (@ 20° C):
3600W
Surge power (5 seconds):
7200W
Efficiency (Full Load):
89%
Minimum DC Fuse Rating:
130A
DC Input Current @ Nominal V DC
Full Load :
115A
No Load :
2A*
Nominal DC Input:
36 VDC
DC Input Voltage Range:
30-45 VDC
Nominal Output Volts:
230 VAC ± 5%
Nominal Output Frequency:
50 Hz
BATTERY CHARGER
Charging Capacity DC:
30A
Acceptance Volts VDC:
Selectable
43.2V/42.6V Wet/Gel
Float Volts VDC:
39.9V Wet/40.8V Gel
Input Voltage AC:
230V
Input Current AC:
12.8A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable:
144**, 163, 182, or 201VAC
Maximum Input AC Volts:
Selectable: 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
30A***
Input Frequency:
45-55 Hz
Maximum Output AC (Continuous):
15.6A
Automatic Transfer Time:
4-6 ms
*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming current.
9906058 230V APS MV-cabinet--English.p65
3/21/00, 4:29 PM
15