Save these instructions, Caution, Toshiba – Toshiba 1500 Plus User Manual
Page 8
TOSHIBA
SAVE THESE INSTRUCTIONS-
This manual contains important instructions
that should be followed during the installation and maintenance of the UPS and it's batteries. Use for
models UE1E1E006-5M, UE1E1E008-5M, UE1E1E010-5M.
- The maximum ambient temperature in which this UPS unit should be operated or stored is
104
°
F (40
°
C).
- The nominal battery voltage range is indicated in Section 5.6.
- Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
- When replacing batteries, use the same number and type of one of the following sealed, lead-acid
batteries (do not mix types of batteries):
Model Capacity
Manufacturer
Type
Quantity
600 VA
Yuasa
NPH5-12FR
5
800 VA
1000 VA
Yuasa
HPH5-12FR
5
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the use of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful
to the eyes and skin and could also be toxic.
This unit contains sealed lead acid batteries. Lack of preventative
maintenance could result in batteries exploding and emitting gasses and/or
flame. Annual preventative maintenance must be performed by an authorized, trained technician.
Failure to replace a battery before it becomes exhausted may cause the
case to crack, possibly releasing electrolytes from inside the battery, and
resulting in secondary faults such as odor, smoke, and fire.
IMPORTANT SAFETY INSTRUCTIONS
CAUTION
CAUTION
WARNING
WARNING
vi
CAUTION