3) SYSTEM METERING - The UPS shall be provided with a single read-
out display which displays, upon request, the following information:

AC INPUT VOLTAGE (Line to Line)

AC OUTPUT VOLTAGE (Line to Line, Line to Neutral)

AC

OUTPUT

CURRENT

BATTERY

VOLTAGE

BATTERY

CHARGING

CURRENT

INPUT

FREQUENCY

OUTPUT

FREQUENCY

INPUT/

OUTPUT

kW

POWER

FACTOR

4) SYSTEM DIAGNOSTICS - The following diagnostic information shall be
provided to troubleshoot the UPS should a fault occur:

UPS Ok

UPS Overload (including Bypass)

Memory Error

Inverter Output Current Limit

Wrong Phase Rotation of AC Input Low Battery Voltage
Internal AC Circuit Fault

I/O not Synchronized

Internal DC Circuit Fault

Auto-transfer Mode

Heatsink Overheat

Fuse Open

DC unbalanced

Battery Discharging Mode

DC Circuit Over/Under voltage

UPS Output Disabled

DC Circuit Overcurrent

Chopper Input Overcurrent

Inverter Overcurrent

Inverter Over/Under voltage

Inverter Overload

5.0 MECHANICAL DESIGN

A.

UPS

Enclosure


The UPS shall be in a freestanding, NEMA1 enclosure equipped with
casters and leveling feet. The overall dimensions and weights shall be as
follows:

UPS Size

Dimensions

Weight

15 kVA

20.0”W x 36.3”D x 59.8”H

783 lbs.