Toshiba 4200FA User Manual

Page 4

background image

4200FA-XT1

May, 2008

4

protection against spikes, common/normal mode noise, load steps and
frequency shifts (without battery back-up capability).

3.0 SYSTEM PARAMETERS

A. UPS Input

1) Input Voltage

480VAC

2) Input Voltage Requirement

3 Phase, 3 Wire + Ground

3) Voltage Variation

+10% to -30%

4) Rated Frequency

50/60 Hz

5) Frequency Range

45 - 65 Hz

6) Power Factor

> 0.98 lagging

7) Input Capacity

110% of UPS Output Capacity

8) Walk-In Function

From 20% to 100% over 5 seconds

9) Input Current Limit

125% of nominal capacity

10) Inrush Current

< 600% under synchronous condition

11) Input Current THD

< 3% Total Harmonic Distortion (THD)

12) Surge Withstandability

Meets ANSI C62.41 (IEEE 587)

13) Input Phase Rotation

Standard front-panel alarm panel shall

(Protection/Detection)

notify user that unit has been supplied

with incorrect phase rotation on input to

allow for correct installation. The UPS

shall be fully protected to prevent

damage

from

this

event.

B. UPS Output

1) Rated Voltage

208/120VAC

2) Output Voltage Requirements 3 Phase, 4 Wire + Ground
3) Output Capacity

15 kVA

4) Rated Load Power Factor

0.8 lagging

5) Voltage Regulation

+/- 2% nominal (balanced load)

+/-

3%

nominal

(unbalanced

load)

6) Voltage Adjust. Range

+/- 5% manually (by front panel user
interface)

7) Phase Displacement

+/- 2 deg. (balanced load)

+/-

4

deg.

(100%

unbalanced

load)

8) Rated Frequency

50/60 Hz (jumper selectable)

9) Frequency Regulation

+/- 0.01% free running

10) Frequency Synch. Range

+/- 0.5/1.0/1.5 Hz (+/- 1.0 Hz Standard)

User

selectable

11) Frequency Slew Rate

1.0 Hz/second to 3.0 Hz/second

12) Voltage Transients

+/- 5% (100% step load change)