3.8. Pulse train input (RP)

The frequency command can be input from the pulse train input.

Parameter

Title

Function

Adjustment range

Default setting

fmod

Frequency setting mode selection 1

1 - 12
11: RP pulse input

2

f234

RP/high speed pulse input point 1 setting

-100 - 100%

0

f235

RP/high speed pulse input point 1 frequency

0.0 - fh Hz

0.0

f236

RP/high speed pulse input point 2 setting

0 - 100%

100

f237

RP/high speed pulse input point 2 frequency

0.0 - fh Hz

60.0

f378

Number of RP terminal input

12 - 9999

500

f660

Override additional input selection

0 - 12
11: RP pulse input

0