beautypg.com

Annotating trends, Drawing on the screen, Screen annotate – Omega Speaker Systems Rercorder RD8300 User Manual

Page 41: 11 turning the unit off

background image

Section 4

– Functional Description

Page 32

09/11/2008 REV 0.99

The following conditions for record on alarm must be met for a recording to start.

Record Setup

External

Trigger

checkbox is checked

The trigger source is

selected

Digital Input Setup

Digital Input set to

Record

and enabled

(Must be same input

as selected in

Record Setup)

Record Mode

The Record

ARM

button has

been pressed

Digital Input

The specified

digital input must

be activated

When the external event is active the unit will start recording. It will continue to record for a minimum of 30
seconds or until the external event is removed.

4.10.3 Email on Alarm Event

The recorder can be set up to send an email on an alarm event. Any alarm can be programmed to

Notify

a

recipient of the event. The email will be sent to the default address entered into the System Setup Menu. It is
also necessary to set up the

smtp

information in the

System Menu

. Finally, in the Alarm Setup menu the

channel must be enabled along with the Notify Enable and the Master enable.

Always make sure the email is functional by manually sending an

email

otherwise if the alarm triggers an

email which cannot be sent, the recorder will try then simply discard it.

The following conditions for email on Alarm event must be met for an email to be sent.

System Setup

SMTP

email

information has been

setup

There must be a

functional

Ethernet

connection

Alarm Setup

Notify

is checked

Alarm Enable

is

checked

Alarm Master Setup

Channel Enable

checked

Master Enable

checked

Notify Enable

checked

Alarm

The specified

alarm must be in

an alarm condition


4.11 Turning the unit off

When power is removed from the unit it does not turn off immediately. There is a battery backup in the power
supply that runs the unit for a couple of minutes to ensure that all systems shut down properly and all data files
are closed and secured. Once the recorder senses the power has been removed it shuts off the display and blinks
the

LED

status indicator on the lower right of the front panel, to show that it is in the battery backup mode. It waits

approximately 30 seconds to ensure that the power failure is not intermittent or simply a brown out, then
commences the shut down procedure. If power should return during this period then the recorder resumes
operation normally. When the recorder completes the shutdown process, it turns the battery off and the unit is
OFF.

There are a few cautionary measures that need to be taken:

1. Ensure that the backup battery switch on the

rear panel

is in the ON position when using the unit and

DO NOT USE THIS SWITCH TO TURN OFF THE UNIT.

2. If the unit has been off for a lengthy period, the battery may require up to 72 hours to fully charge.

3. If you RESET the unit using the button recessed behind the media door, you may lose data if you do not

STOP RECORDING and SAVE THE CONFIGURATION FILE.