Annotating trends, Drawing on the screen, Screen annotate – Omega Speaker Systems Rercorder RD8300 User Manual
Page 41: 11 turning the unit off
Section 4
– Functional Description
Page 32
09/11/2008 REV 0.99
The following conditions for record on alarm must be met for a recording to start.
Record Setup
checkbox is checked
The trigger source is
selected
Digital Input Setup
Digital Input set to
(Must be same input
as selected in
Record Setup)
Record Mode
The Record
been pressed
Digital Input
The specified
digital input must
be activated
When the external event is active the unit will start recording. It will continue to record for a minimum of 30
seconds or until the external event is removed.
4.10.3 Email on Alarm Event
The recorder can be set up to send an email on an alarm event. Any alarm can be programmed to
recipient of the event. The email will be sent to the default address entered into the System Setup Menu. It is
also necessary to set up the
. Finally, in the Alarm Setup menu the
channel must be enabled along with the Notify Enable and the Master enable.
Always make sure the email is functional by manually sending an
otherwise if the alarm triggers an
email which cannot be sent, the recorder will try then simply discard it.
The following conditions for email on Alarm event must be met for an email to be sent.
System Setup
information has been
setup
There must be a
connection
Alarm Setup
checked
Alarm Master Setup
Alarm
The specified
alarm must be in
an alarm condition
4.11 Turning the unit off
When power is removed from the unit it does not turn off immediately. There is a battery backup in the power
supply that runs the unit for a couple of minutes to ensure that all systems shut down properly and all data files
are closed and secured. Once the recorder senses the power has been removed it shuts off the display and blinks
the
status indicator on the lower right of the front panel, to show that it is in the battery backup mode. It waits
approximately 30 seconds to ensure that the power failure is not intermittent or simply a brown out, then
commences the shut down procedure. If power should return during this period then the recorder resumes
operation normally. When the recorder completes the shutdown process, it turns the battery off and the unit is
OFF.
There are a few cautionary measures that need to be taken:
1. Ensure that the backup battery switch on the
is in the ON position when using the unit and
DO NOT USE THIS SWITCH TO TURN OFF THE UNIT.
2. If the unit has been off for a lengthy period, the battery may require up to 72 hours to fully charge.
3. If you RESET the unit using the button recessed behind the media door, you may lose data if you do not