Step 3: testing the thermostat – Robertshaw 9620 User Manual

Page 7

background image

Step 3: Testing the Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL
TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: D

O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW

50°F (10°C). T

HIS CAN DAMAGE

THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY

.

1. Place the COOL-OFF-HEAT-EM

switch into the COOL position

2. Press the

button until the temperature

setting is at least 3 degrees below the room temperature. The air
conditioning system should turn on within a few seconds.

NOTE: O

NCE THE THERMOSTAT TURNS THE SYSTEM OFF WHILE IN THE COOL OR HEAT MODE

,

A BUILT

-

IN DELAY KEEPS THE COM

-

PRESSOR FROM TURNING ON FOR ABOUT

5

MINUTES

. T

HIS PROTECTS THE COMPRESSOR

. N

O ADDITIONAL TIME DELAY RELAY

(

DELAY ON

BREAK

)

IS NECESSARY

. T

O OVERRIDE THE

5-

MINUTE DELAY FOR INSTALLATION

,

PRESS

RESET. T

HIS WILL ERASE THE DELAY AS WELL

AS ALL PROGRAMMING

.

3. Put the COOL-OFF-HEAT-EM switch into

the OFF position. The air conditioning
system should turn off. The fan may
continue to run for a short period of time.

4. Put the COOL-OFF-HEAT-EM switch

into the HEAT position.

5. Press the

button until the temperature setting is at least

3 degrees above room temperature. The heating system should turn
on. The fan may not turn on immediately, depending on the fan delay
built into the furnace.

6. Put the COOL-OFF-HEAT-EM switch

into the OFF position. The heating
system should turn off. Once again,
the fan may have a delay.

7. Put the

AUTO-ON switch

to the ON position. The blower
fan should turn on.

8. Put the

AUTO-ON switch

to the AUTO position. The blower
fan should turn off.

7

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

AUTO - ON

AUTO - ON

>

>