Terminal legend - 9620 – Robertshaw 9620 User Manual
Page 6

6
12. Install two AA ENERGIZER
®
brand batteries or equivalent into battery
compartment. Be sure to match positive (+) ends of batteries with
positive (+) battery terminals in the battery compartment.
13. Replace cover on thermostat by snapping into place.
14. Turn on power to system. Test thermostat as described in the
following section.
TERMINAL LEGEND - 9620
TERM
EQUIPMENT TO CONNECT
REQ?
TERMINAL FUNCTION
C
24VAC common connection
Yes
For input of 24VAC common
side of transformer
L
System fault indicator connection
No
For connection of system
fault indicator (if present)
R
24VAC hot connection
Yes
For input of 24VAC hot side
of transformer
Y2
Second stage cooling connection
No
Energizes on a call for sec-
ond stage cooling
Y1
First stage compressor connection
Yes
Energizes on a call for first
stage heating or cooling
E
Emergency heat connection
No*
Energizes on a call for heat
in the EM mode only
G
Indoor fan connection
Yes
Energizes with E, Y1, Y2 and
W2 terminals or with FAN
option switched to the ON
position
W2
Second stage heat connection
No*
Energizes on a call for sec-
ond stage of heat (auxiliary
heat)
O
Cool active reversing
Yes**
Energizes when in the in
valve connection
COOL mode
B
Heat active reversing
Yes**
Energizes when in the
valve connection
HEAT or EM modes
* For systems using a backup heat source. If separate E terminal connection is not available,
jumper E and W2.
** Most heat pump systems will have a cool active OR a heat active reversing valve. Use the
appropriate terminal.