12. Install two AA ENERGIZER

®

brand batteries or equivalent into battery

compartment. Be sure to match positive (+) ends of batteries with
positive (+) battery terminals in the battery compartment.

13. Replace cover on thermostat by snapping into place.

14. Turn on power to system. Test thermostat as described in the

following section.

TERMINAL LEGEND - 9620

TERM

EQUIPMENT TO CONNECT

REQ?

TERMINAL FUNCTION

C

24VAC common connection

Yes

For input of 24VAC common
side of transformer

L

System fault indicator connection

No

For connection of system
fault indicator (if present)

R

24VAC hot connection

Yes

For input of 24VAC hot side
of transformer

Y2

Second stage cooling connection

No

Energizes on a call for sec-
ond stage cooling

Y1

First stage compressor connection

Yes

Energizes on a call for first
stage heating or cooling

E

Emergency heat connection

No*

Energizes on a call for heat
in the EM mode only

G

Indoor fan connection

Yes

Energizes with E, Y1, Y2 and
W2 terminals or with FAN
option switched to the ON
position

W2

Second stage heat connection

No*

Energizes on a call for sec-
ond stage of heat (auxiliary
heat)

O

Cool active reversing

Yes**

Energizes when in the in

valve connection

COOL mode

B

Heat active reversing

Yes**

Energizes when in the

valve connection

HEAT or EM modes

* For systems using a backup heat source. If separate E terminal connection is not available,

jumper E and W2.

** Most heat pump systems will have a cool active OR a heat active reversing valve. Use the

appropriate terminal.