Gas fireplaces, P36d only, Venting arrangements - horizontal terminations – Regency Zero Clearance Direct Vent Gas Fireplace P36D-NG1 User Manual

Page 6: Vertical height (feet) horizontal (feet)

background image

16

2

2

0

0

12

12

6

6

18

4

40-1/2"
(1029mm)
Minimum
Height
Requirement

4

14

8

8

10

10

14

16

18

20

V

ertical

Height

(Feet)

Horizontal (Feet)

P36D ONLY

Please refer to Page 11 (Exterior Vent Terminations)

for additional guidelines on vent locations.

P36 - P36D Gas Fireplace

Venting Arrangements - Horizontal

Terminations

This diagram shows all allowable combinations of vertical runs with
horizontal terminations, using one 90º elbow (two 45º

elbows equal

one 90º elbow).

The lightly shaded area,

6

8

2

0

4

10

0

2

4

6

40

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

12

, in the diagram shows allowable

combinations when installing a P36

The darker shaded area,

6

8

2

0

4

10

0

2

4

6

40

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

12

, in the diagram shows additional allowable

combinations when installing a P36D.

Note: Must use optional fl ue adapter (Part # 510-994) when using

Rigid Pipe.

Maintain clearances to combustibles.

Horizontal vent must be supported every 3 feet.

Firestops are required at each fl oor level and whenever passing

through a wall.

A vent guard may be required as per local codes, refer to page 11 for
“Exterior Vent Termination Locations”.

Note: FPI Direct Vent System (Flex) is only approved for horizontal

terminations.

40

June 2007 Regency Product Specifi cations Book

Gas Fir

eplaces

Gas Fireplaces