Framing and Finishing

1)

Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front
of the unit. Total facing thickness can vary from 1/2” (13mm) to
1-1/4” (32mm) thick.

2)

Frame in the enclosure for the unit with framing material.

Note: Header for the P36 must be installed vertically to maintain
clearances to combustible materials. Non combustible header may
be installed horizontally.

3)

For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)

4)

The top of the unit must not be closer than 32” (813mm) to the
ceiling.

5)

Combustible material may be brought up to the top and sides of
the unit and be covered with ceramic tiles, bricks, rock or other
suitable combustible fi nishing materials.

If using the Barcelona Surround, Kensington, Balmoral, or
Tripoli Screen Door please note that framing and facing must
be non combustible (12” on top and 6” on both sides) and that
the Barcelona is only approved for installation with a single
sidewall.

Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0” to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).

6)

Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.

Drywall

Mantel Clearances

2

0

12

6

4

8

10

0

Side View

Top of

Unit

12" (305mm)

3-1/2" (89mm)

7-1/2"(191mm)

A

To base

of Unit

Standof

f

B

C

D

6" Side Wall

5"

2"

Mantel

leg

Mantel

leg

P36 - P36D

Allowable mantel leg

projection.

3"

1-1/2"

8" Single Sidewall when using the Barcelona Surrround

Mantel Clearances

A

B

C

D

with Flush Glass or

Hampton Cast

30-1/2”

(778mm)

14” (356mm)

10” (254mm)

7” (178mm)

with Bay Option

30-1/2”

(778mm)

13” (330mm)

10” (254mm)

7” (178mm)

with Flush Glass and

Barcelona Surround

30-1/2”

(778mm)

17” (432mm)

12” (305mm)

8” (203mm)

with Tripoli Screen Door,

Kensington, or Balmoral

Front

30-1/2”

(778mm)

20” (508mm)

N/A

12” (305mm)

P36 - P36D Gas Fireplace

Combustible Mantels

Because of the extreme heat this fi replace emits, the mantel
clearances are critical.
Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.

Note: If desired a non-combustible mantel may be installed at a

lower height.

Note: Ensure the paint that is used on the mantel and the facing

is “heat resistant” or the paint may discolour.

Mantel Leg Clearances

Combustible mantel leg clearances as per diagram below:
Clearances are from the fi nished edge of the unit or an installed front.

Maximum
1-1/2” projection at 2”
minimum clearance.

WARNING

Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.

Clearance:

Dimension

Measured From:

A: Mantel Height

7” (178mm)

Minimum (Additional on this page)

B: Sidewall

6” (152mm)

Side of installed front

Sidewall: Barcelona Only

8” (203mm)

Approved for single sidewall only

C: Ceiling

32” (813mm)

Top of installed unit

D: Mantel Depth

12” (305mm)

Maximum (Additional on this page)

E: Alcove Width

48” (1219mm)

Sidewall to Sidewall (Minimum)

F: Alcove Depth

36” (914mm)

Front to back wall (Maximum)

Top of Hearth must not be higher than the base of the fi rebox.

Vent Clearances

Clearance Dimension

Horizontal - Top

2” (51mm)

Horizontal - Side

1-1/2” (38mm)

Horizontal - Bottom

1-1/2” (38mm)

Vertical (Flex or Rigid)

1-1/4” (32mm)

E

B

B

A

C

D

F

Clearance Requirements

36

June 2007 Regency Product Specifi cations Book

Gas Fir

eplaces

Gas Fireplaces