beautypg.com

Raypak XPAK 120 User Manual

Page 8

background image

8

Fault display

Faults are displayed with EXXX, where XXX is the

default code generated by either the remote control

unit or the boiler. The code is displayed instead of the

time on the information line. The signal is fixed if the

alarm does not require a RESET while it flashes if it

requires the RESET procedure. Table A shows the

fault codes generated by the thermostat timer.

For definitions of the alarms generated by the boiler,

please consult the XPak Installation and Operating

Instructions.

Fig. 6: Fault display

Error #

Description

E 201

No communication with boiler. Data

transmission to the boiler must be

checked.

E 81

EEPROM Error

This code means the memory of the ter-

mostat timer has been altered (e.g. via

EMV). Following the error, the default

data is loaded.

All the set values must be checked.

E 80

Fault in the ambient temperature sensor.

Table A: Fault codes generated by the thermostat timer

Reset blocks in case of boiler error

Some boiler alarms can be directly reset from the

remote control unit. In these cases, in addition to the

code flashing on the display, a triangle lights up next to

the RESET message on the right-hand side of the dis-

play (see Fig. 6). At this point, the RESET function can

be activated. Turn the EDIT knob clockwise. A

RESET command equivalent to pressing the button on

the boiler is generated and the release command is

sent to the boiler. The arrow disappears after the

RESET command has been given.

Technical menu

To enter the technical menu, turn the SELECT knob

to “MODE,” turn the EDIT knob to “PL” and then

select the required parameter using the SELECT

knob.

Turn the EDIT knob to set the required value.

To exit the technical level, select the forward/back

parameter, “PL,” using the SELECT button and then

turn the EDIT knob.

Both heating program 2 and some installer parame-

ters can be set in the technical menu.

To set the heating program, parameters 01-07, con-

sult the above section

Fig. 7: Reset blocks in case of boiler error