beautypg.com

Preventive maintenance schedule – Raypak MVB 503-2003 User Manual

Page 49

background image

49

densate management system or drain, as required

by local codes.

3. Check that area is free from combustible materi-

als, gasoline, and other flammable vapors and

liquids.

4. Check air filter and replace as necessary.

5. Follow pre-start-up check in the Start-up section.

6. Visually inspect burner flame. It should be light

blue at full input. Remove and visually inspect hot

surface igniter and sensor for damage, cracking or

debris build-up.

7. Check operation of safety devices. Refer to manu-

facturers’ instructions.

8. Follow oil-lubricating instructions on pump (if re-

quired). Over-oiling will damage pump.

Water-lubricated circulators do not need oiling.

9. To avoid potential of severe burn, DO NOT REST

HANDS ON OR GRASP PIPES. Use a light touch;

return piping will heat up quickly.

10. Check blower and blower motor.

11. Check for piping leaks around pumps, relief valves

and other fittings. Repair, if found. DO NOT use

petroleum-based stop-leak.

Periodically

1. Check relief valve. Refer to manufacturer’s

instructions on valve.

2. Test low water cut-off (if equipped). Refer to manu-

facturer’s instructions.

Preventive Maintenance

Schedule

The following procedures are recommended and are

good practice for all MVB installations.

Daily

1. Check gauges, monitors and indicators.

2. Check instrument and equipment settings. (See

“Post Start-Up Check” on page 45.)

3. Check burner flame. (Should see light blue flame

at full input rate).

Weekly

For low-pressure heaters, test low-water cut-off

device. (With heater in pre-purge, depress the low

water cut-off test button. Appliance should shut-off

and ignition fault light should come on. Depress reset

button on front of heater control panel to reset).

Monthly

1. Check flue, vent, stack, or outlet dampers.

2. Test blower air pressure. (See “Blower Check” on

page 42.)

3. Test high and low gas pressure interlocks (if

equipped). (See “Safety Inspection” on page 43.)

Semi-Annually

1. Recalibrate all indicating and recording gauges.

2. Check flame failure detection system components.

3. Check firing rate control by checking the manifold

pressure. (See “Manifold Check” on page 43.)

4. Check piping and wiring of all interlocks and shut-

off valves.

5. Check air filter and replace as necessary.

Annually

1. Test flame failure detection system and pilot turn-

down.

2. Test high limit and operating temperature. (See

“Post Start-Up Check,” page 45.)

3. Check flame sensor.

4. Conduct a combustion test at full fire. Carbon diox-

ide should be 8.5 to 9.0% at full fire for natural gas,

and between 9.5 to 10.0% for propane gas.

Carbon monoxide should be < 100 ppm.

5. Check valve coil for 60 cycle hum or buzz. Check

for leaks at all valve fittings using a soapy water

solution (while heater is operating). Test other

operating parts of all safety shut-off and control

valves and increase or decrease settings

(depending on the type of control) until the safety

circuit opens. Reset to original setting after each

device is tested.