Fig. 43: High/Low Gas Pressure Switch

The optional high gas pressure switch connection

mounts down-stream of the gas valve. Special ports

are located on the backside of the gas valve and

accessible from the front of the heater (to reset the gas

pressure switch) or through the removable access

panels on the rear of the heater (to reset the gas pres-

sure switch), as necessary. If the gas pressure

regulator in the valve fails, the high gas pressure

switch automatically shuts down the burner.

Operation of either the High or Low Gas Pressure

Switch will turn on an LED inside the switch housing.

Push the top of the plastic switch housing as shown in

Fig. 43 to reset a tripped pressure switch. The LED

will go out when the switch is reset.

Air Pressure Switch

This heater is equipped with an air pressure switch to

prove the operation of the blower before allowing the

ignition control to begin a Call for Heat. It is located on

the right side of the lower flange of the blower mount-

ing assembly, directly behind the junction box.

Fig. 44: Air Pressure Switch

Blocked Vent Switch

This heater is equipped with a blocked vent pressure

switch to prevent the operation of the heater when too

much of the vent is blocked. This switch is located on

the right side of the heater near the right rear corner.

Fig. 45: Blocked Vent Switch

UDB Diagnostic Board

This heater is equipped with a diagnostic board which

will indicate faults as they occur. Refer to the Trouble-

shooting section for instructions on accessing,

reviewing and clearing these faults.

Fig. 46: UDB Diagnostic Board

NOTE: The wiring diagrams in this manual show all

standard options. Refer to the large wiring diagram

provided with your heater for options installed on

your specific unit(s).