TOP VIEW

FRONT VIEW

FRONT VIEW

PROUDLY MADE IN AMERICA

P/N 901889

Note: Current draw (Amps) is for pump only

Water hardness grains per gallon
Soft = 0-4 • Medium = 5-15 • Hard = 16-25

Heater

Side

From Combustible

Surfaces (min.)

For Service

(recommended)

Floor*

0”

0”

Rear

12”

24”

Right Side

1”

1”

Left Side

1”

1”

Top

Indoor
Outdoor

0”

Unobstructed

10”

Unobstructed

Front

Open

24”

Vent Stack Indoor

1”

1”

Vent Cap

Outdoor

12”

12”

CLEARANCES

MVB

Model

Water Hardness

Soft

Medium

Hard

HP

Amps

HP

Amps

HP

Amps

503/504

1/4

6

1/4

6

3/4

11

753/754

1/4

6

1/2

7

3/4

11

1003/1104

1/4

6

1/2

7

1

14

1253

1/2

7

1

14

1

14

1503/1504

3/4

11

1

14

1

14

1753

1

14

1-1/2

15

1-1/2

15

2003/2004

1

14

1-1/2

15

1-1/2

15

*Do not install on carpeting
Note: Local codes may require increased clearances

PUMP

5

All components are contained inside the
cabinet

(except PRV), no external fans or

valves to deal with.