On-Board Diagnostic Center

Raypak’s MVB comes equipped with a microprocessor-controlled diagnostic control center that displays its information on a 2x20 character LCD
display in plain English. This control monitors system safeties, ignition faults and system status, while storing up to 16 reported faults. Raypaks
diagnostic center monitors the fault outputs of the Fenwal ignition control. Converting the Fenwal’s flashing lights into real English fault codes
that anyone can understand. The control is also equipped with a SPDT dry contact relay output that is switched anytime a safety fault occurs.
This can be used for a heater alarm or a BMS safety interface.

CA

TEGOR

Y

I*

BOILERS

(TYPE

H)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

40°F

GPM

P FT

T °F

GPM

P FT

T °F

GPM

P FT

GPM

P FT

GPM

P FT

504

25

1.1

34

100

11.3

8

42

2.7

28

1.4

N/A

N/A

754

32

1.7

40

100

13.8

13

63

6.0

42

2.9

32

1.7

1104

46

4.1

40

113

18.6

16

92

13.3

62

6.7

46

4.1

1504

63

8.0

40

113

22.2

22

N/A

N/A

84

13.3

63

8.0

2004

84

16.0

40

113

27.2

30

N/A

N/A

112

26.9

84

16.0

CA

TEGOR

Y

I*

W

A

TER

HEA

TERS

(TYPE

WH)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

GPM

P FT

T °F

GPM

P FT

T °F

GPM

P FT

GPM

P FT

504

50

2.8

17

100

11.3

8

N/A

N/A

28

1.4

754

50

3.5

25

100

13.8

13

64

6.1

42

3.0

1104

60

6.3

30

113

18.6

16

90

12.6

60

6.3

1504

82

12.6

30

113

22.2

22

N/A

N/A

82

12.6

2004

109

25.5

30

113

27.2

29

N/A

N/A

109

25.5

CA

TEGOR

Y

IV

BOILERS

&

W

A

TER

HEA

TERS

(TYPE

H

&

WH)

MVB

Model

Flow Rates

Pressure Drops

Minimum Flow

Maximum Flow

20°F

30°F

40°F

GPM

P FT

T °F

GPM

P FT

T °F

GPM

P FT

GPM

P FT

GPM

P FT

503

25

1.1

35

100

11.3

9

43

2.8

29

1.4

N/A

N/A

753

33

1.9

40

100

13.8

13

65

6.4

43

3.1

33

1.9

1003

43

3.7

40

113

18.6

15

87

12.0

58

6.0

43

3.7

1253

54

6.2

40

113

22.2

19

109

20.9

73

10.2

54

6.2

1503

65

9.5

40

113

25.5

23

N/A

N/A

87

16.0

65

9.5

1753

76

13.4

40

113

27.2

27

N/A

N/A

101

22.5

76

13.4

2003

87

15.2

40

116

30.2

30

N/A

N/A

116

31.9

87

18.9

6

*Category I with vertical vent, category III with horizontal venting and no extractor.
† Minimum flow 50GPM for WH hot water supply.
‡ Use 30° column as minimum flow for hot water supply.

Boiler Only

Diagnostic Information

Safety Faults

Ignition Control Faults

Condensate Drain

Low Air

Manual High Limit

Flame- No CFH

Auto High Limit

Ignition Lockout

Low Water Cut-off

Low HSI Current

Vent Pressure

Low 24VAC

High Gas Pressure

Internal Control Fault

Low Gas Pressure

Controller Alarm

Flow Switch

Blower Switch

Factory Option

External Interlock

Cold Water Run