16.6 Cooling Coil Safety Devices

16.6.1 Cooling Coil Frost Thermostat

The sensing element for this device is inserted into
the pocket of the cooling coil situated through the
access hole in the coil cover.

The frost thermostat has two settings marked as set
point with an arrow head and "diff". The control
should be set at 5° C with a 1° C differential.

To replace, remove screw and pull off knob.
Remove cover. Disconnect wires.
Pull the sensing element out of the pocket in the coil.
Replace in reverse order.

16.6.2 Pressure Switches

The coil and dirty filter pressure switches are preset
and different. They are differential pressure switches
measuring the pressure loss across the coil or filter.

Coil Pressure Switch
(Normally open contact) used to prove adequate air
flow for safe operation of cooling coil.

Filter Pressure Switch
(Normally open contact) used to give indication of
filter becoming blocked.

To replace, remove coil compartment cover.
Disconnect wires noting their position. Remove the
flexible tubing noting the position of the tube
connection. Replace in reverse order and check
operation.

Figure 18: Cooling Coil Safety Devices.

Coil Frost Thermostat

set at 5°C with 1°C diff.

Filter

White

White

Red

Red

Coil Pressure Switch

set at 0.57 mbar (.23 in wc)

Filter Pressure Switch

set at 1.17 mbar (.47 in wc)

Negative

Pressure

Positive

Pressure

Set

Point

N.O

Connections

Description

Part Number

Coil Pressure Switch

90439801

Filter Pressure Switch

90439804

Coil Frost Thermostat

K018