beautypg.com

Roberts Gorden DAT100 User Manual

Page 23

background image

SECTION 10: W

IRING

AND

E

LECTRICAL

I

NFORMATION

17

10.3 DAT Main Circuit Board Terminal Identification

Terminal

Number

Use

Relay/Function

Operation

1 Input or Output

External Fan Control

Input for Remote Fan Opera-

tion Output for Fan Operation

Monitor

Optional - Main Fan Runs from

External Control

2 Output

230 V to external control

230 V 50 Hz supply of external

thermostat or control

3 Input

Burner On

Burner Fires.

R1 energizes with gas valve

Burner Operates.

Fan Operates via R1

4 Output

230 V Burner ON Signal

Optional Remote Indication of

Burner ON.

5 Output

Neutral for Signals

& External Control

7 Output

230 V Burner Lockout Signal

Optional Remote Indication of

Burner Lockout

8 Input

Burner Lockout Reset from N

(5)

Optional Remote Burner Lock-

out Reset (must be from N)

9 & 10

Volt Free Safety Circuits for

External Condensers

Site Wiring to Condensers

Normally Closed Controls

Break on Fault Position

DualAir

®

units contains Coil

Frost Thermostat, Coil Pres-

sure Switch & Auxiliary Contact

on Contactor

11 Input

230 V 1st Stage of Cooling

(Free Cooling)

R2 On

Burner OFF

Fan ON from R2

Dampers Output to T16

12 Input

230 V 2nd Stage of Cooling

Cooling Coil Stage 1

R2 OFF

R3 ON

Burner OFF

Fan ON from R3

Dampers Output to T15

Output to Condenser 1 at T17

& 18

13 Input

230 V 3rd Stage of Cooling

Cooling Coil Stage 2

R3 ON
R4 ON

All input 12 Operations

Output to Condenser 2 at T19

& 20

14, 15 & 16 Output

230 V Output for Optional

Damper

From R2

14 = Neutral

15 = Recirculated Air

16 = Fresh Air

17 & 18

Volt Free Control Circuit

Condenser 1

R3 ON

Normally Open Contact

for Condenser 1

19 & 20

Volt Free Control Circuit

Condenser 2

R3 ON
R4 ON

Normally Open Contact

for Condenser 2

21 & 22 Output

230 V Output to

Remote Dirty Filter Warning

21 = L

22 = N

23 & 24

Volt Free Output to

Remote Dirty Filter Warning

Alternative Dirty Filter Indica-

tion for BMS or DualAir

®

Con-

trol

Normally Open Contact

for Dirty Filter Indication

25 & 26 Input

0 - 10 V DC Input for

Modulating Burner

T3 Must Be Live to Operate

Burner

0 V = Minimum Fire

10 V = Maximum Fire

This manual is related to the following products: