beautypg.com

Start – Roberts Gorden DAT100 User Manual

Page 38

background image

D

UAL

A

IR

®

H

EATING

AND

COOLING

U

NITS

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

32

15.3 Troubleshooting for Flame Supervision System

Repair or replace as

necessary.

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44 (0) 1902 498733

www.combat.co.uk

or www.rg-inc.com

Control box faulty.

Replace with correct type.

Use section 15.1 to

trace the fault.

Heater Operating

TROUBLESHOOT ENDS.

No

Repair or replace as

necessary.

Is inlet burner gas pressure

correct? Is live and neutral

polarity correct? Is

flame probe circuit correct?

Is there a current flowing in

the flame probe circuit with no

flame present?

Yes

No

Does “lockout” occur when

there is a flame present?

Yes

Is the connecting lead

damaged? Is the flame probe

damaged or touching earthed

components?

No

Is the green light on and

at least 1 µA DC fame

current?

Connect a DC ammeter in

series with the flame probe.

Yes

No

Yes

Yes

No

START

NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.

This manual is related to the following products: