beautypg.com

Roberts Gorden 175 User Manual

Page 42

background image

UHA S

TANDARD

U

NIT

H

EATER

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

34 of 51

Heat Exchanger

Make sure there are no cracks.

See Page 19, Section 9.

Make sure there is no sagging, bending or distortion.

Clean or replace as required.

Gas Line and Shut-off
Valves

Check for gas leaks.

See Page 19, Section 9.

Burner Observation
Window

Make sure it is clean and free of cracks or holes.

Clean and replace as required.

Flue Blower Scroll, Wheel
and Motor

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Inshot Burners and
Orifices

Clear of obstructions (even spider webs will cause problems).

Carefully remove any dust and debris from the burner.

Direct-Spark Igniter

Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.

The electrode gap should be 1/8" (3.2 mm).

Thermostat

There should be no exposed wire or damage to the device or wiring.

See Page 21, Section 10.

Suspension Points

Make sure the heater is hanging securely.

Look for signs of wear on the suspension materials or ceiling.

See Page 10, Figure 5.

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.

Gas Valve

Verify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.

Verify all wiring connections.

Condensate Drain
(when installed)

Flush drain and clear any obstructions.

Wall Tag

If a wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON

®

independent distributor if

you need a wall tag.

See Page 5, Section 2.1.

This manual is related to the following products: