Figure 9: Separated Combustion Heater - Vertical and Horizontal Vent Termination
Figure 10: Concentric Vent Box
12" (31 cm)
Minimum from air inlet to vent
termination.
Vent
Termination
Listed Thimble through
Combustible Wall
Vent**
12" (31 cm)
Minimum from wall
to vent termination.
Air Intake
12" (31 cm)
Minimum from air inlet to vent
termination.
Air Intake
Termination
NOTE: Vent supports not shown
Vent**
Air Intake*
12" (31 cm)
Minimum from roof to vent
termination.
Vertical
Option
Horizontal
Option
90°
Bend
Model
**Vent Diameter
Part Number
UHA[X]S 150 - 400
4" (10 cm)
90502102
Model
*Air Intake Diameter
Part Number
UHA[X]S 150 - 250
4" (10 cm)
90502102
UHA[X]S 300 - 400
5" (13 cm)
90502105
4" (10 cm) Single
Wall Vent Pipe
(By Others)
Seal joint between single wall
and Type B vent with silicone sealant.
Use 3 sheetmetal
screws equally
spaced around joint.
Use 3 sheetmetal
screws equally
spaced around collar.
Concentric
Vent Box
6" (15 cm) or 8" (20 cm)
Single Wall Inlet Air Pipe
(By Others)
One piece of 4" (1
0 cm) diamet
er, 1/4" (6 cm)air
space t
ype
“B”
vent.
Selkir
k Model R
V or e
quiv
alent.
(By other
s)
Combustion Air
to Heater
Toward
Outside
Exhaust
from Heater
4" (10 cm) or
5" (13 cm)